Owon XDM 3051
Home / Owon XDM 3051
Owon Benchtop Digital MultimeterXDM 3051 Supplier
OWON XDM3051X 5 1/2 Digital MultiMeter
- 4 inch 480 x 320 pixels high resolution LCD
- resolutions up to 5 1/2 digits
- reading rates up to 150 readings/s
- true RMS AC voltage / current measurement
dual line display supported - the change trend analysis accessible via special chart mode
- SCPI supported – remote control, and data-sharing
possible via LAN, USB, RS232 port, and WiFi*
* WiFi module is optional - multi- IO interface: USB Device / Host, RS232, LAN, and ext.
trigger input
4 inches LCD display, more vision to check the data, support dual display. Trends and chart mode display.
Dual display
Data-logger Mode
During recording the measurement value, possible to set the logging duration (min. 5ms), and length, then get access to chart or table result. Mikado Electronics is the best Owon Benchtop Digital MultimeterXDM 3051 Supplier in Kolkata, India.
Specifications
OWON XDM3051
XDM3051 | Measurement Range | Frequency Range | Accuracy: 1 Year ±(% of reading +% of range) |
DC Voltage | 200mV, 2V, 20V, 200V, 1000V | / | 0.015±0.004 |
True RMS AC Voltage | 200mV, 2V, 20V, 200V, 750V | 20 Hz – 45 Hz | 1.5 + 0.10 |
45 Hz – 20 kHz | 0.2 + 0.05 | ||
20 kHz – 50 kHz | 1.0 + 0.05 | ||
50 kHz – 100 kHz | 3.0 + 0.05 | ||
DC Current | 200.000 μA | / | 0.055 + 0.005 |
2.00000 mA | 0.055 + 0.005 | ||
20.0000 mA | 0.095 + 0.020 | ||
200.000 mA | 0.070 + 0.008 | ||
2.00000 A | 0.170 + 0.020 | ||
10.0000 A | 0.250 + 0.010 | ||
True RMS AC Current | 20.0000 mA, 200.000 mA, 2.00000 A, 10.0000 A |
20 Hz – 45 Hz | 1.5 + 0.10 |
45 Hz – 2 kHz | 0.50 + 0.10 | ||
2 kHz – 10 kHz | 2.50 + 0.20 | ||
Resistance | 200.000 Ω | / | 0.030 + 0.005 |
2.00000 kΩ | 0.020 + 0.003 | ||
20.0000 kΩ | 0.020 + 0.003 | ||
200.000 kΩ | 0.020 + 0.003 | ||
2.00000 MΩ | 0.040 + 0.004 | ||
10.0000 MΩ | 0.250 + 0.003 | ||
100.000 MΩ | 1.75 + 0.004 | ||
Diode Test | 2.0000 V | / | 0.05 + 0.01 |
Continuity | 2000 Ω | / | 0.05 + 0.01 |
Frequency Period | 200 mV – 750 V | 20 Hz – 2 kHz | 0.01 + 0.003 |
2 kHz – 20 kHz | 0.01 + 0.003 | ||
20 kHz – 200 kHz | 0.01 + 0.003 | ||
200 kHz – 1 MHz | 0.01 + 0.006 | ||
20 mA – 10 A | 20 Hz – 2 kHz | 0.01 + 0.003 | |
2 kHz – 10 kHz | 0.01 + 0.003 | ||
Capacitance | 2.000 nF | 200 nA | 3 + 1.0 |
20.00 nF | 200 nA | 1 + 0.5 | |
200.0 nF | 2 μA | 1 + 0.5 | |
2.000 μF | 10 μA | 1 + 0.5 | |
200 μF | 100 μA | 1 + 0.5 | |
10000 μF | 1 mA | 2 + 0.5 | |
Temperature | temperature sensors under 2 categories supported – thermocouple (ITS-90 conversion between B / E / J / K / N / R / S / T type), and thermal resistance (RTD sensor conversion between Pt100 and Pt385 type) |
||
Data-logger Function | |||
Logging Duration | 5ms | ||
Logging Length | 1M points |