Motwane 10 KPI
Home / Motwane 10 KPI
Motwane 10 KPI
Application
The Insulation Resistance test is an essential test that helps to verify the condition of electrical insulation. The insulation resistance quality of an electrical system degrades with time, and with environmental conditions such as temperature, humidity, moisture, and dust particles. This instrument is designed for routine insulation resistance testing and diagnostic testing like PI, DD, DAR & SV of high voltage electrical apparatus Including transformers, generators, motors, cables, bushings, LA’s, switchgear, etc., and is temperature independent. The data trends can reveal vital information about the insulation quality and enable the user to make informed decisions.
Features
- Available IR testing with multiple diagnostic modes – PI, DAR, DD, Step Voltage, BDV & Burn test
- Programmable test voltage from 500V-10KV
- Insulation resistance range from 1K ohm to 20T ohm
- Three programmable timers
- Programmable break down current settings
- Mains & battery operation
- Internal data storage up to 1000 tests*
- Galvanic isolated RS 232 & USB port
- Application software for data trends analysis
- AC/DC voltage measurement of up to 600V
- Auto calibration at every start up
- Burn mode for uninterrupted insulation resistance testing
- Alarm mode with min-max setting & pass-fail indication
- CAT IV 600V, IP54, complies with latest IEC/IS standards
Test voltage
- Voltage Selectable : 500V,1KV, 2.5KV, 5KV, 7.5KV, 10KV
- Programmable : 500V to 1KV in 10 V steps
- 1 KV to 10 KV in 25 V steps
- Voltage Accuracy: ±5%
- Short Circuit Current: 3mA
- Resistance Range:
- Analog Display: 1 K ohm to 10 T ohm
- Digital Display: 1 K ohm to 20 T ohm
- Accuracy : ±5% (Upto 999G ohm )
- : ±10% (1T ohm to 10T ohm )
- : ±20% (10T ohm to 20T ohm )
- Programmable Timer : T1,T2 &T3 (0-99Min 59sec)
- Current Measurement
- Range : 0-3mA
- Accuracy : ±5% of reading + 5 digits
- Voltage Measurement
- Range : 0-600V
- Accuracy : ±8% of reading + 5 digits
- Capacitance Measurement
- Range : 1nF to 50µF
- Accuracy : ±5% of reading + 5 digits
- Noise Rejection
- 1mA RMS per kV test voltage, not exceeding 5mA
- Memory
- Internal data storage up to 1000 tests*
- PC Interface
- Galvanic isolated USB & RS232
- Display
- Large LCD display with a backlight